Out.P Output phase loss detected
98
The Out.P trip indicates that phase loss has been detected at the drive output.
If Pr 05.042 = 1, the physical output phases are reversed, and so sub-trip 3 refers to physical output phase V and sub-trip 2
refers to physical output phase W.
Recommended actions:
Check motor and drive connections
To disable the trip set Output Phase Loss Detection Enable (06.059) = 0
OV DC bus voltage has exceeded the peak level or maximum continuous level for 15 seconds
2
The OV trip indicates that the DC bus voltage has exceeded the VM_DC_VOLTAGE[MAX] or
VM_DC_VOLTAGE_SET[MAX] for 15 s. The trip threshold varies depending on voltage rating of the drive as shown below.
Sub-trip Identification
Recommended actions:
Increase deceleration ramp (Pr 00.004)
Decrease the braking resistor value (staying above the minimum value)
Check nominal AC supply level
Check for supply disturbances which could cause the DC bus to rise
Check motor insulation using an insulation tester
Trip Diagnosis
Sub-trip Reason
1 U phase detected as disconnected when drive enabled to run.
2 V phase detected as disconnected when drive enabled to run.
3 W phase detected as disconnected when drive enabled to run.
4
The drive output frequency is above 4 Hz and a phase is disconnected for the time
specified by Output Phase Loss Detection Time (06.058).
NOTE
Voltage rating VM_DC_VOLTAGE[MAX] VM_DC_VOLTAGE_SET[MAX]
100 510 400
200 510 400
400 870 800
Source xx y zz
Control
system
00 0
01: Instantaneous trip when the DC bus voltage exceeds
VM_DC_VOLTAGE[MAX].
Control
system
00 0
02: Time delayed trip indicating that the DC bus voltage is above
VM_DC_VOLTAGE_SET[MAX].
Power
system
01 0
00: Instantaneous trip when the DC bus voltage exceeds
VM_DC_VOLTAGE[MAX].