Returns or sets the rated motor voltage in Volts for instance 1. This attribute is linked to
Pr 0.05.009.
Returns or sets the rated motor voltage in Volts for instance 2. This attribute is linked to
Pr 0.21.009.
Rated frequency
Returns or sets the rated motor frequency in Hertz for instance 1. This attribute is linked
to Pr 0.05.006.
Set Pr 0.05.006 = RatedFreq1 * 10.
Get RatedFreq1 = Pr 0.05.006 / 10.
Returns or sets the rated motor frequency in Hertz for instance 2. This attribute is linked
to Pr 21.006.
Set Pr 0.21.006 =RatedFreq2 * 10.
Get RatedFreq2 = Pr 0.21.006 / 10.
Name: RatedVoltage1
Class 0x28 Default Pr 0.05.009
Instance 0x01 Data Type USINT
Attribute 0x07 Access Get/Set
Name: RatedVoltage2
Class 0x28 Default Pr 0.21.009
Instance 0x02 Data Type USINT
Attribute 0x07 Access Get/Set
Name: RatedFreq1
Class 0x28 Default Pr 0.05.006 / 10
Instance 0x01 Data Type USINT
Attribute 0x09 Access Get/Set
Name: RatedFreq2
Class 0x28 Default Pr 0.21.006 / 10
Instance 0x02 Data Type USINT
Attribute 0x09 Access Get/Set