EasyManua.ls Logo

Emerson Unidrive M700 - Page 77

Emerson Unidrive M700
198 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SI-Ethernet User Guide 77
Issue: 1
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started Parameters
Key features
and Protocols
PC Applications Security Diagnostics
Glossary of
terms
Index
This parameter reports the link’s status if it has been loaded. A Reset (S.10.002) is
required to load any changes.
6.1.5 Menu 11 – Synchronization
This Ethernet interface will be preferred as the grandmaster over others with higher
preferred values or none specified. A value of zero will ensure that the Ethernet
interface will not become grandmaster (making the Ethernet interface act as an IEEE
1588 slave device only). If more than one Ethernet interface has the same preferred
value only one will be chosen as the grandmaster using the IEEE 1588 BMC algorithm.
The parameter does not guarantee that the Ethernet interface will become grandmaster
but a value of zero guarantees that the Ethernet interface will not become a
grandmaster.
Specifies the clock domain for the Ethernet interface to act as a grandmaster clock.
This parameter displays the MAC address, as a 64-bit hexadecimal value, of the
-3 Invalid args Link number / argument zero or invalid
-2 Too many links Maximum number of links has been reached
-1 Out of memory Failed to allocate memory
0 OK Configuration of link successful
1 Not running Ok, not running
2 OK sync Configuration of synchronous link successful
Value Text Description
S.11.001 Preferred Sync Master
Minimum 0 Maximum 4
Default 1 Units
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, BU
S.11.002 Master Clock Domain
Minimum 0 Maximum 3
Default 0 Units
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, BU
S.11.005 Grandmaster MAC Address
Minimum
0
(Display: 00:00:00:00:00:00)
Maximum
18446744073709551615
(Display: FF:FF:FF:FF:FF:FF)
Default Units
Type 64 Bit Volatile Update Rate Background write
Display Format MAC Address Decimal Places 0
Coding RO, ND, NC, PT, BU