EasyManua.ls Logo

Emerson XJAL-020Z-CFV-012 - Table 3 - Medium Temp Performance Criteria for R-404 A; Table 4 - Low Temp Performance Criteria for R-404 A

Emerson XJAL-020Z-CFV-012
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2017 Emerson Climate Technologies, Inc.
24
AE5-1377 R3
Table 3 - Medium Temp Performance Criteria for R-404A
For other approved refrigerant performance data, visit Online Product Information at Emerson.com/OPI
H.P.
Medium Temperature
Model Number
Btu/hr @ +25°F Sat. Suction
Temp / 90°F Ambient
Btu/hr @ +25°F Sat. Suction
Temp / 100°F Ambient
Refrigerant/
Oil Type
1.5
XJAM-015Z-CFV
14600
13600
R404A / POE
2
XJAM-020Z-CFV
19600
17900
R404A / POE
2
XJAM-020Z-TFC
19600
17900
R404A / POE
3
XJAM-030Z-CFV
28500
25900
R404A / POE
3
XJAM-030Z-TFC
28500
25900
R404A / POE
4
XJAM-040Z-CFV
38600
35300
R404A / POE
4
XJAM-040Z-TFC
38600
35300
R404A / POE
5
XJAM-050Z-CFV
47100
43800
R404A / POE
5
XJAM-050Z-TFC
47100
43800
R404A / POE
6
XJAM-060Z-TFC
54600
50200
R404A / POE
Table 4 - Low Temp Performance Criteria for R-404A
For other approved refrigerant performance data, visit Online Product Information at Emerson.com/OPI
H.P.
Low Temperature
Model Number
Btu/hr @ -10°F Sat. Suction
Temp / 90°F Ambient
Btu/hr @ -10°F Sat. Suction
Temp / 100°F Ambient
Refrigerant/
Oil Type
2
XJAL-020Z-CFV
13100
12700
R404A / POE
2
XJAL-020Z-TFC
13100
12700
R404A / POE
3
XJAL-030Z- TFC
17200
16400
R404A / POE
3
XJAL-035Z- CFV
19700
18100
R404A / POE
4
XJAL-040Z-CFV
24700
23700
R404A / POE
4
XJAL-040Z-TFC
24700
23700
R404A / POE
5
XJAL-050Z-CFV
27600
25700
R404A / POE
5
XJAL-050Z-TFC
27600
25700
R404A / POE
6
XJAL-060Z-TFC
34700
32700
R404A / POE

Table of Contents