Possible Error and Solution
Discharge
Temperatures over
270°F
-Stop the Unit
-Display DLT trip on
diagnostic
-Auto start the unit
after 3 minutes
-Lockout unit if 6 trips
within 1 hour
-Check system operations, for example
condensing pressures, return gas
temperatures, envelope operations etc.
Verify operations and correct the
situation
-Contact open at 435
psig ±22psig
-Contact Close at
348 psig ±22psig
-Stop the Unit
-Display HP trip on
diagnostic
-Auto start the unit
after 3 minutes
-Lockout unit if 6 trips
within 1 hour
-Display HP lockout on
diagnostic
-Verify condenser fan operation,
excessive air recirculation, excessive
ambient temperatures, incorrect
envelope operations
-Verify system component operations
-Stop the Unit
-Display over current
trip on diagnostic
-Lockout unit if 6 trips
in less than 12 hour
-Display over current
lockout on diagnostic
* Check rotary switch, make sure it is
on the right position according to the
unit model, Reference Table 7
* Check system operating pressures
* Check voltage supply at the
compressor terminals, must be with in
the +/- 10% voltage tolerance of the
compressor nameplate.
Discharge Gas
Overheat
(XJAM
Models)
Discharge
Temperatures over
270°F
-Stop the Unit
-Display DLT trip on
diagnostic
-Lockout unit if 6 trips
within 1 hour
-Display DLT overheat
lockout on diagnostic
-Check system operations, for example
condensing pressures, return gas
temperatures, envelope operations etc.
Verify operations and correct the
situation
-Contact open at 435
psig ±22psig
-Contact Close at
348 psig ±22psig
-Stop the Unit
-Display HP trip on
diagnostic
-Lockout unit if 6 trips
within 1 hour
-Display HP lockout on
diagnostic
-Verify condenser fan operation,
excessive air recirculation, excessive
ambient temperatures, incorrect
envelope operation
-Verify system component operations