1598030330 XR30CX MRS GB r2.0 23.05.2013.doc XR30CX 3/3
14. DEFAULT SETTING VALUES
Label Name Range Default Menu
rtc Real time clock menu - - Pr1
CF Temperature measurement unit
°C °F
°F Pr2
rES Resolution
in=integer; dE= dec.point
in Pr2
EdF Defrost mode
rtc - in
in Pr1
IdF Interval between defrost cycles
1 120 ore
8 Pr1
MdF (Maximum) length for defrost
0 255 min
45 Pr1
dFd Displaying during defrost
rt, it, SEt, DEF
dEF Pr2
dAd MAX display delay after defrost 0 ÷ 255 min 0 Pr2
Fdt Draining time 0÷120 min 0 Pr2
Hur Current hour 0÷23 - rtc
Min Current minute 0 ÷ 59 - rtc
dAY Current day Sun ÷ SAt - rtc
Hd1 First weekly holiday Sun÷ SAt – nu nu Pr2
Hd2 Second weekly holiday Sun÷ SAt – nu nu Pr2
Ld1 1
st
workdays defrost start 0 ÷ 23h 50 min. - nu 6.0 rtc
Ld2 2
nd
workdays defrost start 0 ÷ 23h 50 min. - nu
13.0
rtc
Ld3 3
rd
workdays defrost start 0 ÷ 23h 50 min. - nu 21.0 rtc
Ld4 4
th
workdays defrost start 0 ÷ 23h 50 min. - nu nu rtc
Ld5 5
th
workdays defrost start 0 ÷ 23h 50 min. - nu nu rtc
Ld6 6
th
workdays defrost start 0 ÷ 23h 50 min. - nu nu rtc
Sd1 1
st
holiday defrost start 0 ÷ 23h 50 min. - nu 6.0 Pr2
Sd2 2
nd
holiday defrost start 0 ÷ 23h 50 min. - nu
13.0
Pr2
Sd3 3
rd
holiday defrost start 0 ÷ 23h 50 min. - nu 21.0 Pr2
Sd4 4
th
holiday defrost start 0 ÷ 23h 50 min. - nu nu Pr2
Sd5 5
th
holiday defrost start 0 ÷ 23h 50 min. - nu nu Pr2
Sd6 6
th
holiday defrost start 0 ÷ 23h 50 min. - nu nu Pr2
Adr Serial address 0÷247 1 Pr2
onF on/off key enabling nu, oFF; ES oFF Pr2
rEL Software release -- 9.1 Pr2
Ptb Map code -- -- Pr2