nPS
Pressure switch number: (0 to 15) Number of activation of the pressure switch, during the “d#d
interval, before signaling the alarm event (I2F= PAL). If the nPS activation in the did time is reached,
switch off and on the instrument to restart normal regulation.
odc
Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr = Compressor OFF;
F_C = Compressor and fan OFF.
rrd
Outputs restart after doA alarm: No = outputs not affected by the doA alarm; Yes = outputs restart
with the doA alarm.
RTC SUBMENU (if present)
CbP Clock Presence (N to Y): permits disabling or enabling of the clock.
Hur Current hour (0 to 23 hours)
Min Current minute (0 to 59 minutes)
dAY Current day (Sun to Sat)
Hd1 First weekly holiday (Sun to nu) Set the first day of the week that follows the holiday times.
Hd2 Second weekly holiday (Sun to nu) Set the second day of the week that follows the holiday times.
Hd3 Third weekly holiday (Sun to nu) Set the third day of the week that follows the holiday times.
ILE
Energy Saving cycle start during workdays: (0 to 23 hours, 50 mintes) During the Energy Saving
cycle the setpoint is increased by the value in HES so that the operation setpoint is SET + HES.
dLE
Energy Saving cycle length during workdays: (0 to 24 hours 00 minutes) Sets the duration of the
Energy Saving cycle on workdays.
ISE Energy Saving cycle start on holidays. (0 to 23 hours 50 minutes)
dSE Energy Saving cycle length on holidays (0 to 24 hours 00 minutes)
Ld1 to Ld6
Workday defrost start (0 to 23 hours 50 minutes) These parameters set the beginning of the 6
programmable defrost cycles during workdays. For example, when Ld2 = 12.4 the second defrost
starts at 12.40 during workdays.
Sd1 to Sd6
Holiday defrost start (0 to 23 hours 50 minutes) These parameters set the beginning of the 6
programmable defrost cycles on holidays. For example, when Sd2 = 3.4 the second defrost starts at
3.40 on holidays.
ENERGY SAVING
HES
Temperature increase during the Energy Saving cycle: (-30 to 30°C / -54 to 54°F) sets the increasing
value of the setpoint during the Energy Saving cycle.
PEL
Energy saving activation when light is switched off: (N to Y)
n = function disabled.
Lig= energy saving is activated when the light is switched off and vice versa.
AUS= energy saving is activated when the AUX is switched off and vice versa.
LEA= energy saving is activated when the light & the AUX relays are switched off and vice versa.
LAN MANAGEMENT
LMd Defrost synchronization: Y= the section send a command to start defrost to other controllers, N= the
section that will not send a global defrost command.
dEM Type of end defrost: N= the of the LAN defrost are independent; Y= the end of the defrost are
synchronization.
LSP L.A.N. setpoint synchronization: Y= the section setpoint, when modified, is updated to the same
value on all the other sections; N= the setpoint value is modified only in the local section.
LdS L.A.N. display synchronization: Y= the value displayed by the section is sent to all the other sections;
N= the setpoint value is modified only in the local section.
LOF L.A.N. On/Off synchronization this parameter states if the On/Off command of the section will act on
all the other ones too: Y= the On/Off command is sent to all the other sections; N= the On/Off
command acts only in the local section.
Parameter Description
Table 13-1 - Parameter List