Document Part # 026-4280 Rev 1 Page 24 of 33
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
LLi L.A.N. light synchronization this parameter states if the light command of the section will act on all
the other ones too: Y= the light command is sent to all the other sections; N= the light command acts
only in the local section.
LAU L.A.N. AUX output synchronization this parameter states if the AUX command of the section will act
on all the other ones too: Y= the light command is sent to all the other sections; N= the light command
acts only in the local section.
LES L.A.N. energy saving synchronization this parameter states if the energy saving command of the
section will act on all the other ones too: Y= the Energy Saving command is sent to all the other
sections; N= the Energy Saving command acts only in the local section.
LSd Remote probe display: this parameter states if the section has to display the local probe value or the
value coming from another section: Y= the displayed value is the one coming from another section
(that has parameter LdS = y); N= the displayed value is the local probe one.
LCP P4 probe sent via LAN (N, Y)
StM Cooling activation via LAN: N= not used; Y= a generic cooling requests from LAN activate the
solenoid valve connected to compressor relay.
ACE Cold Calling in LAN always enabled even if the compressor block: (N,Y)
PROBE CONFIGURATION
P1C Probe 1 configuration: (nP – Ptc – ntc – PtM) nP= not present; PtC= Ptc; ntc= NTC; PtM= Pt1000
OF1
Probe 1 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the thermostat
probe.
P2C Probe 2 configuration: (nP – Ptc – ntc – PtM) nP= not present; PtC= Ptc; ntc = NTC; PtM= Pt1000.
OF2
Probe 2 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offsets of the evaporator
probe.
P3C Probe 3 configuration: (nP – Ptc – ntc – PtM) nP= not present; PtC= Ptc; ntc = NTC; PtM= Pt1000.
OF3 Probe 3 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the probe 3.
P4C Probe 4 configuration: (nP – Ptc – ntc – PtM) nP= not present; PtC= Ptc; ntc = NTC; PtM= Pt1000.
OF4 Probe 4 calibration: (-12.0 to 12.0°C/ -21 to 21°F) allows to adjust possible offset of the probe 4.
SERVICE – OTHERS
LCL Light on during cleaning mode (N,Y)
FCL Fan on during cleaning mode (N,Y)
MAP
Map used during standard operation (1°M, 2°M, 3°M, 4°M) It sets the map used by the controller
among the four possible maps.
MP1
Alternate Map enabled by digital input or MODBUS command (1°M, 2°M, 3°M, 4°M) It sets the
alternate map enabled by digital input or MODBUS command among the four possible maps.
CLt Cooling time percentage: it shows the effective cooling time calculated by XM600 during regulation.
tMd Time to next defrost: it shows time before the next defrost if interval defrost is selected.
LSn L.A.N. section number (1 to 8) Shows the number of sections available in the L.A.N.
Lan
L.A.N. serial address (1 to LSn) Identifies the instrument address inside local network of multiplexed
cabinet controller.
Adr
RS485 serial address (1 to 247): Identifies the instrument address when connected to a MODBUS
compatible monitoring system.
br It sets the baud rate among: (96 = 9.6 bit/s; 192 = 19.2 bit/s)
Parameter Description
Table 13-1 - Parameter List