46 • XM679K I&O Manual 026-1218 Rev 4
Ld5 nu Pr1 Workdays Fifth defrost start
Ld4 to 23.5(143) - nu(144)
(hours.10min)
Ld6 nu Pr1 Workdays Sixth defrost start
Ld5 to 23.5(143) - nu(144)
(hours.10min)
Sd1 nu Pr1 Holidays First defrost start
0.0 to 23.5(143) - nu(144)
(hours.10min)
Sd2 nu Pr1 Holidays Second defrost start
Sd1 to 23.5(143) - nu(144)
(hours.10min)
Sd3 nu Pr1 Holidays Third defrost start
Sd2 to 23.5(143) - nu(144)
(hours.10min)
Sd4 nu Pr1 Holidays Fourth defrost start
Sd3 to 23.5(143) - nu(144)
(hours.10min)
Sd5 nu Pr1 Holidays Fifth defrost start
Sd4 to 23.5(143) - nu(144)
(hours.10min)
Sd6 nu Pr1 Holidays Sixth defrost start
Sd5 to 23.5(143) - nu(144)
(hours.10min)
ENERGY SAVING
ESP P1 Pr1 Energy saving probe selection
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5) - tEr(6)
HES 0.0 Pr1
Temperature increasing during Energy
Saving
[-54°F to 54°F]
[-30.0°C to 30.0°C]
PEL n Pr1
Energy saving activation when Light
switched off
n(0) – Y(1)
LAN MANAGEMENT
LMd y Pr2 Defrost Synchronization n(0) – Y(1)
dEM y Pr2 Defrost end Synchronization n(0) – Y(1)
LSP n Pr2 SET-POINT Synchronization n(0) – Y(1)
LdS n Pr2
Display Synchronization (temperature
sent via LAN)
n(0) – Y(1)
LOF n Pr2 ON/OFF Synchronization n(0) – Y(1)
LLi y Pr2 Light Synchronization n(0) – Y(1)
LAU n Pr2 AUX Synchronization n(0) – Y(1)
LES n Pr2 Energy Saving Synchronization n(0) – Y(1)
LSd n Pr2 Remote probe displaying n(0) – Y(1)
LPP n Pr2 Pressure value sent in LAN n(0) – Y(1)
StM n Pr2
Cooling request from LAN enable
compressor relay
n(0) – Y(1)
PROBE CONFIGURATIONS
P1C NtC Pr2 P1 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
ot 0.0 Pr2 P1 calibration
[-21°F to 21°F]
[-12.0°C to 12.0°C]
P2C NtC Pr2 P2 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
oE 0.0 Pr2 P2 calibration
[-21°F to 21°F]
[-12.0°C to 12.0°C]
P3C NtC Pr2 P3 configuration nP(0) - Ptc(1) - ntc(2) - PtM(3)
o3 0.0 Pr2 P3 calibration
[-21°F to 21°F]
[-12.0°C to 12.0°C]
Table 23-1 - Default Setting Values (Continued)