EasyManua.ls Logo

Emerson XR75CX - Modbus Termination Blocks

Emerson XR75CX
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 • XR75CX I&O Manual 026-1210 Rev 0 09-FEB-2011
18.3.MODBUS Termination
Blocks
Because the XR75CX device has no on-board
means of termination, use the MODBUS termination
block (P/N 535-2711) for termination that can be
wired to the end of the cable segment using the three-
pin connector. Wire the two signal wires to the out-
side terminals, and connect the shield to pin 18 of the
device, keeping the exposed shield wire length as
short as possible (3 inches ideal maximum length).
Figure 18-8 - MODBUS Termination Block (P/N 535-2711)
SHIELD WIRE
(CONNECT TO
OF LAST DEVICE)
PIN 18
FROM OTHER
DEVICES
TO LAST DEVICE
AT END OF DAISY
CHAIN

Table of Contents

Related product manuals