MODBUS Termination Blocks Default Setting Values • 29
doA Door open alarm delay 0 to 255 min 15 Pr1
nPS Number of activation of pressure switch 0 to 15 15 Pr2
Odc Compress status when open door no; Fan; CPr; F_C F-C Pr2
rrd Regulation restart with door open alarm n – YyPr2
HES Differential for Energy Saving (-30°C to 30°C) (-54°F to 54°F) 0 Pr2
Hur* Current hour 0 to 23 - Pr1
Min* Current minute 0 to 59 - Pr1
dAY* Current day Sun to SAt - Pr1
Hd1* First weekly holiday Sun to SAt – not used not used Pr1
Hd2* Second weekly holiday Sun to SAt – not used not used Pr1
ILE* Energy Saving cycle start during workdays 0 to 23 hr 50 min 0.0 Pr1
dLE* Energy Saving cycle length during workdays 0 to 24 hr 00 min 0 Pr1
ISE* Energy Saving cycle start on holidays 0 to 23 hr 50 min 0.0 Pr1
dSE* Energy Saving cycle length on holidays 0 to 24 hr 00 min 0 Pr1
Ld1*
1
st
workdays defrost start
0 to 23 hr 50 min - not used
6.0 Pr1
Ld2*
2
nd
workdays defrost start
0 to 23 hr 50 min - not used
13.0 Pr1
Ld3*
3
rd
workdays defrost start
0 to 23 hr 50 min - not used
21.0 Pr1
Ld4*
4
th
workdays defrost start
0 to 23 hr 50 min - not used
not used Pr1
Ld5*
5
th
workdays defrost start
0 to 23 hr 50 min - not used
not used Pr1
Ld6*
6
th
workdays defrost start
0 to 23 hr 50 min. - not used
not used Pr1
Sd1*
1
st
holiday defrost start
0 to 23 hr 50 min - not used
6.0 Pr1
Sd2*
2
nd
holiday defrost start
0 to 23 hr 50 min - not used
13.0 Pr1
Sd3*
3
rd
holiday defrost start
0 to 23 hr 50 min - not used
21.0 Pr1
Sd4*
4
th
holiday defrost start
0 to 23 hr 50 min - not used
not used Pr1
Sd5*
5
th
holiday defrost start
0 to 23 hr 50 min - not used
not used Pr1
Sd6*
6
th
holiday defrost start
0 to 23 hr 50 min - not used
not used Pr1
Adr Serial address 1 to 247 1 Pr2
pbC Kind of probe Pt1000; ntc ntc Pr2
onF ON/OFF key enabling not used, oFF; ES not used Pr2
dP1 Room probe display -- - Pr1
dP2 Evaporator probe display -- - Pr1
dP3 Third probe display -- - Pr1
dP4 Fourth probe display -- - Pr1
rSE Real set actual set - Pr2
rEL Software release -- 2.6 Pr2
Ptb Map code -- - Pr2
Label Name Range Value Level
Table 19-1 - Default Setting Values (
*
Only for models with real time clock (RTC),
2
Only for XR75CX with X-REP output)