12
Humidity Alarm Function Selection Parameter ( Default = 0 )
Temperature Alarm Set Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum parameter.
( Default = 50.0 °C )
Alarm Set Maximum Parameter ( Default = Maximum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from temperature
alarm set value parameter to maximum value of the device scale.
Alarm Set Minimum Parameter (Default = Minimum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from minimum value of
device scale to temperature alarm set maximum parameter value.
Temperature Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
( Default = 0)
Temperature Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
( Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Humidity Alarm Set Parameter
This parameter value can be programmed between humidity minimum alarm set
parameter and humidity alarm set maximum parameter.
( Default = 50 )
Humidity (Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
Humidity alarm.
Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
Humidity Set Maximum Parameter(Default =Maximum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from humidity alarm set
minimum parameter to maximum value of the device scale.
Alarm
Humidity (Default = 0)
Humidity
Alarm On Delay Time Parameter
Alarm On Delay Time can be defined with this parameter. It can be adjusted
from 0 to 99 minutes.
Humidity Set Minimum Parameter(Default =Minimum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from minimum value of
device scale to humidty alarm set maximum parameter value.
Alarm
Humidity Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Temperature Alarm Function Selection Parameter ( Default = 1 )
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.