Chronothermostat with Humidistat User Manual
• Temperature regulation:
- ON/OFF with differential setting between 0.1°C and 1°C
- PROPORTIONAL with proportional band and regulation period setting
• Weekly programming
• Daily resolution: 1h
• Activation delay setting between 15, 30 and 45 minutes (independent for every hour)
• Measured temperature scale: 0°C ÷ +50°C
• Measured and displayed temperature resolution: 0.1°C
• Temperature regulation range: 2.0°C ÷ +50°C
• Measurement update: every 20 seconds
• Measurement precision: ± 0.5°C
• Winter or summer or manual operation
• Temperature display in °C, °F, P°c, P°f
HUMIDISTAT
• Selectable humidification or deumidification operation
• ON/OFF type regulation with settable differential between 5% RH and 20% RH
• Measurement precision: ± 5% RH
• Resolution: 1% RH
• Setting range: 30% ÷ 90% RH
• Automatic change CET / DST
• Password protected keypad lock for installation in public places
• Wall mounting (or on 503 type box)
• Terminal strip for cables with 1.5mm
2
maximum section
• Operating temperature: 0 °C ÷ +50 °C
• Operating humidity: 20% ÷ 90% noncondensing
• Storage temperature -10°C ÷ +65°C
• Degree of protection: XXD
• Insulation: reinforced among accessible parts (frontal) and all other terminals
• Class of the temperature control according to European Commission communication
2014/C 207/02: class IV. Contribution to seasonal energy efficiency: 2%
The preset temperature values (expressed in °C) are the following:
funct. winter funct. summer
T1 5.0 OFF
T2 15.0 23.0
T3 18.0 25.0
T
MANUAL 20.0 24.0
Regulation of temperature levels is subjected to the following condition: T1 ≤ T2 ≤T3.
In summer mode, T1 cannot be set and corresponds to the air conditioning OFF.