Operating menu Levelflex FMP56, FMP57 FOUNDATION Fieldbus
170 Endress+Hauser
• Digital output 2
• Digital output 3
• Digital output 4
• Digital output 5
• Digital output 6
• Digital output 7
• Digital output 8
Factory setting Off
Additional information The Digital output AD 1 and Digital output AD 2 options refer to the Advanced
Diagnostic Blocks. A switch signal generated in these blocks can be transmitted via the
switch output.
Assign limit
Navigation Setup → Advanced setup → Switch output → Assign limit
Prerequisite Switch output function (→ 169) = Limit
Description Select process variable for limit monitoring.
Selection • Off
• Level linearized
• Distance
• Interface linearized
*
• Interface distance
*
• Thickness upper layer
*
• Terminal voltage
• Electronic temperature
• Measured capacitance
*
• Relative echo amplitude
• Relative interface amplitude
*
• Absolute echo amplitude
• Absolute interface amplitude
*
Factory setting Off
Assign diagnostic behavior
Navigation Setup → Advanced setup → Switch output → Assign diag. beh
Prerequisite Switch output function (→ 169) = Diagnostic behavior
Description Select diagnostic behavior for switch output.
* Visibility depends on order options or device settings