Liquiphant FTL31 Mounting
Endress+Hauser 15
ø >50 (2.0)
<5 m/s (16 ft/s)
ø >10 (0.4)
G 3/4
316L
A0021357
 8 Position of the tuning fork in pipes. Unit of measurement mm (in)
5.1.8 Installation in vessels
If installed horizontally, pay attention to the position of the tuning fork to ensure that the
liquid can drip off.
The electrical connection, e.g. M12 plug, should be established with the cable pointing
downwards. This can prevent moisture from penetrating.
A0021034
 9 Position of the fork in the case of horizontal installation in a vessel
5.1.9 Distance from wall
Ensure that there is sufficient distance between the expected buildup on the tank wall and the
fork. Recommended distance from wall ≥10 mm (0.39 in).