Electrical connection Liquiphant FTL31
18 Endress+Hauser
6 Electrical connection
The device has two operating modes: maximum safety (MAX) and minimum safety (MIN). By
choosing the corresponding operating mode, the user ensures that the device also switches in
a safety-oriented manner even in an alarm condition, e.g. if the power supply line is
disconnected.
Maximum safety (MAX)
The device keeps the electronic switch closed as long as the liquid level is below the fork.
Sample application: overfill protection
Minimum safety (MIN)
The device keeps the electronic switch closed as long as the fork is immersed in liquid.
Sample application: Dry running protection for pumps
The electronic switch opens if the limit is reached, if a fault occurs or the power fails
(quiescent current principle).
6.1 Connecting the device
In accordance with IEC/EN61010 a suitable circuit breaker must be provided for the
device.
6.1.1 Electronic version 3-wire DC-PNP
3-wire DC-PNP is preferably used in conjunction with programmable logic controllers (PLC),
DI modules as per EN 61131-2. Positive signal at the switch output of the electronics (PNP).
Voltage source: non-hazardous contact voltage or Class 2 circuit (North America).
Connection with M12 plug
Depending on the analysis of the switch outputs, the device works in the MAX (maximum
safety) or MIN (minimum safety) mode.
A cable is optionally available
A0022901
 10 M12 plug