Mounting Liquiphant FTL64
12 Endress+Hauser
316L/G1
A0042348
 8 Markings to align the tuning fork
Installing in pipes
Flow velocity up to 5 m/s with a viscosity of 1 mPa⋅s and density of 1 g/cm
3
(SGU).
Check for correct functioning in the event of other process medium conditions.
The flow will not be significantly impeded if the tuning fork is correctly aligned and the
marking is pointing in the direction of flow.
The marking is visible when installed.
A0034851
 9 Installation in pipes (take fork position and marking into consideration)
Screwing in the device
Turn by the hex bolt only, 15 to 30 Nm (11 to 22 lbf ft)
Do not turn at the housing!