Installation Micropilot FMR51, FMR52 PROFIBUS PA
12 Endress+Hauser
6 Installation
6.1 Installation conditions
6.1.1 Mounting position
A
1 2
3
A0016882
Recommended distance A from wall
to outer edge of nozzle: ~ 1/6 of tank
diameter.
Nevertheless the device should not be
installed closer than 15 cm (5.91 in)
to the tank wall.
Not in the center (2), as interference
can cause signal loss.
Not above the fill stream (3).
It is recommended to us a weather
protection cover (1) in order to protect
the device from direct sun or rain.