Commissioning (via operating menu) Micropilot FMR51, FMR52 PROFIBUS PA
44 Endress+Hauser
9.5 Configuration of a level measurement
F
L
D
E
100%
0%
R
A0016933
1. Setup → Tag description
Enter tag for measuring point.
2. Setup → Device address
Enter bus address of the device (only in case of software addressing).
3. Setup → Distance unit
Select distance unit.
4. Setup → Tank type
Select tank type.
5. Setup → Tube diameter (only for "Tank type" = "Bypass/pipe")
Enter the diameter of the stilling well or bypass.
6. Setup → Medium group
Specify medium group ("Water based": DC>4 or "Others": DC>1,9)
7. Setup → Empty calibration
Enter empty distance E (Distance from reference point R to the 0% level)
4)
.
4) If the measuring range covers only an upper part of the tank or silo (E << tank/silo height), it is mandatory to
enter the acutal tank or silo height into the "Setup → Advanced Setup → Level → Tank/silo height" parameter. If
there is an outlet cone, the tank or silo height should not be adjusted as usually E is not << tank/silo height in
these applications.