Micropilot FMR51, FMR52 PROFIBUS PA Commissioning (via operating menu)
Endress+Hauser 45
8. Setup → Full calibration
Enter full distance F (Distance from the 0% to the 100% level).
9. Setup → Level
Indicates the measrued level L.
10. Setup → Distance
Indicates the measured distance from the reference point R to the level L.
11. Setup → Signal quality
Indicates the quality of the evaluated level echo.
12. Setup → Mapping → Confirm distance
Compare distance indicated on the display to real distance in order to start the
recording of an interference echo map.
13. Setup → Advanced setup →Level → Level unit
Select level unit: %, m, mm, ft, in (Factory setting: %)
The response time of the device is preset by the Tank type parameter. An enhanced
setting is possible in the Advanced setup submenu.
9.6 User-specific applications
For details of setting the parameters of user-specific applications, see separate
documentation:
BA01125F (Operating Instructions, FMR51/FMR52, PROFIBUS PA)
For the Expert submenu refer to:
GP01018F/00/EN (Description of Device Parameters, FMR5x, PROFIBUS PA)