Operating Instructions
Micropilot FMR51, FMR52
FOUNDATION Fieldbus
Free space radar
BA01121F/00/EN/03.16
71344019
01.01.zz (Device firmware)

Table of Contents

Other manuals for Endress+Hauser Micropilot FMR52

Questions and Answers

  • J
    Joe SpencerSep 8, 2025
    Why is the measured value incorrect on my Endress+Hauser Micropilot FMR52 Radar?
    • M
      mejiakaitlynSep 8, 2025
      If the measured value on your Endress+Hauser Radar is incorrect, check and adjust the Empty calibration parameter and the Full calibration parameter. If necessary, check and adjust linearization. For measurements in bypasses or stilling wells, select the correct Tank type (Bypass / pipe) and enter the correct diameter in the Tube diameter parameter. You may also need to enter the correct value in the Level correction parameter.
  • W
    walkeramySep 6, 2025
    Why does Endress+Hauser Micropilot FMR52 display a level when the tank is empty?
    • W
      William RomanSep 7, 2025
      If the Endress+Hauser Radar displays a level when the tank is empty, it's likely due to an interference echo. Perform a mapping over the entire measuring range when the tank is empty by using the Confirm distance parameter.
  • G
    glambertAug 22, 2025
    Why Endress+Hauser Micropilot FMR52 Radar device does not respond?
    • J
      John JonesAug 22, 2025
      If your Endress+Hauser Radar device isn't responding, it could be due to the following reasons: * The supply voltage is not connected. In this case, connect the correct voltage. * The cables do not contact the terminals properly. Ensure electrical contact between the cable and the terminal.
  • B
    Bryan MartinezSep 4, 2025
    Why CDI communication does not work with Endress+Hauser Micropilot FMR52 Radar?
    • K
      Kevin AguirreSep 4, 2025
      If CDI communication is not working with your Endress+Hauser Radar, it could be due to a wrong setting of the COM port on the computer. Check the setting of the COM port on the computer and change it if necessary.
  • C
    Carl ParkerSep 3, 2025
    What to do if "Communication error" is indicated on the Endress+Hauser Micropilot FMR52 display?
    • T
      tthompsonSep 3, 2025
      If a "Communication error" is indicated on the display of your Endress+Hauser Radar when starting the device or connecting the display, it could be due to: * Electromagnetic interference. Check the grounding of the device. * A broken display cable or display plug. Exchange the display.
  • P
    Paul CalderonSep 1, 2025
    Why during filling/emptying the measured value jumps downwards on Endress+Hauser Radar?
    • C
      Chelsea WiseSep 1, 2025
      If, during filling or emptying, the measured value jumps downwards on your Endress+Hauser Radar, it could be caused by multiple echoes. To address this: * Check the Tank type parameter. * If possible, avoid a central installation position. * If appropriate, consider using a stilling well.
  • H
    Helen MartinAug 31, 2025
    How to fix invisible values on Endress+Hauser Micropilot FMR52 Radar display?
    • V
      Veronica JonesAug 31, 2025
      If the values on your Endress+Hauser Radar display are invisible, here are some things to try: * The contrast setting may be too weak or too strong. Increase contrast by pressing the appropriate buttons simultaneously or decrease contrast by pressing the appropriate buttons simultaneously. * The plug of the display cable may not be connected correctly. Connect the plug correctly. * The display may be defective. Replace the display.
  • M
    Mary JohnsonAug 30, 2025
    What to do if Endress+Hauser Radar displays a level when the tank is empty?
    • P
      Patrick HoweAug 30, 2025
      If your Endress+Hauser Radar displays a level when the tank is empty, it is likely due to an interference echo. Carry out mapping over the entire measuring range when the tank is empty.
  • J
    john56Aug 28, 2025
    Why Endress+Hauser Micropilot FMR52 device measures incorrectly?
    • Z
      Zachary FarleyAug 28, 2025
      If your Endress+Hauser Radar device is measuring incorrectly, it may be due to a parametrization error. Check and adjust the parameterization.
  • B
    benjamin10Aug 27, 2025
    How to fix error message F941 or S941 "Echo lost" on Endress+Hauser Micropilot FMR52?
    • C
      Crystal KhanAug 27, 2025
      The error message F941 or S941 "Echo lost" on your Endress+Hauser Radar indicates that the level echo is too weak or suppressed. To resolve this: * Check the Medium group parameter. If necessary, select a more detailed setting in the Medium property parameter. * Optimize the alignment of the antenna. If necessary, select a better installation position and/or larger antenna. * If the level echo is suppressed, delete the mapping and record it again.

Summary

Important Document Information

Basic Safety Instructions

Requirements for the Personnel

Specifies qualifications and authorizations for personnel working with the device.

Designated Use

Defines the intended application and measured materials for the device.

Installation

Installation Conditions

Details mounting positions and environmental conditions for proper installation.

Electrical Connection

Connection Conditions

Explains terminal assignments and cable specifications for PROFIBUS PA/FOUNDATION Fieldbus.

Connecting the Device

Provides step-by-step instructions for connecting the device to power.

Integration into a FOUNDATION Fieldbus Network

Commissioning via Wizard

Commissioning via Operating Menu

Configuration of a Level Measurement

Details the parameters for configuring level measurements in liquids.

Commissioning (Block-based Operation)

Block Configuration

Covers preparatory steps and configuration of Resource and Transducer Blocks.

Diagnostics and Troubleshooting

General Trouble Shooting

Provides solutions for general errors like display issues or communication problems.

Diagnostic Information on Local Display

Explains how diagnostic messages and status signals are displayed locally.

Diagnostic Event and Event Text

Details how to identify faults using diagnostic events and texts.

Operating Menu

Setup Menu

Details parameters within the Setup menu, like distance unit and tank type.

Diagnostics Menu

Outlines the diagnostic functions including actual and previous diagnostics.

Endress+Hauser Micropilot FMR52 Specifications

General IconGeneral
Device TypeRadar Level Transmitter
Frequency80 GHz
Housing MaterialAluminum, stainless steel
Ingress ProtectionIP66/IP67
Accuracy± 2 mm
Output Signal4 to 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus
Process ConnectionFlange, thread
Power Supply10 to 30 V DC
ApprovalsATEX, FM, CSA
ApplicationLevel measurement of liquids, pastes, and solids
Process Temperature-40 to 200 °C