Micropilot FMR60/62/67
Endress+Hauser 17
The following parameters affect the safety function and cannot be freely configured in increased
safety mode or in expert mode. Instead they are automatically changed by the device at the start of
the SIL/WHG confirmation to the safety-oriented values mentioned.
Parameter Preset value
Setup → Advanced setup → Safety settings → Output echo lost Alarm
Setup → Advanced setup → Display → Backlight Disable
Diagnostics → Simulation → Assign measurement variable Off
Diagnostics → Simulation → Current output 1 to 2 simulation Off
Diagnostics → Simulation → Device alarm simulation Off
Diagnostics → Simulation → Diagnostic event simulation Off
Expert → Sensor → Distance → Velocity filter Off
Expert → Output → Current output 1 → Trim Off
Expert → Output → Current output 2 → Trim Off
Expert → Diagnostics → Simulation → Simulation distance on Off
The following parameters affect the safety function. If the settings differ from the as-delivered state
of the device, only expert mode is available for selection in the SIL/WHG confirmation. Values can
not be specified as the delivery state depends on the order code.
Parameter Parameter name
Setup → Advanced setup → Level Medium type
Setup → Advanced setup → Current output 1 Current span
Setup → Advanced setup → Current output 2 Current span
Expert → Sensor → Distance Blocking distance evaluation mode
Expert → Sensor → Envelope curve
Envelope curve statistic
Envelope smoothing mode
FAC window size
Max Value EWC
Expert → Sensor → Sensor properties Antenna zero distance
Expert → Sensor → Mapping
Mapping Threshold
Mapping window size
Expert → Sensor → First echo factor First echo factor
Expert → Sensor → Echo fine adjustment
Parabolic fit window size
Edge correction
Expert → Sensor → Tank bottom evaluation Tank bottom range
Expert → Sensor → Echo tracking Moving track recognition