Micropilot FMR67B HART Operation options
Endress+Hauser 27
 Cover screwed down correctly?
 Cover lock tightened correctly?
12 Operation options
12.1 Overview of operating options
Operation via operating keys and DIP switches on the electronic insert
Operation via optical operating keys on the device display (optional)
Operation via Bluetooth® wireless technology (with optional device display with Bluetooth)
with Smartblue app or FieldXpert, DeviceCare
Operation via operating tool (Endress+Hauser FieldCare/DeviceCare, handheld terminal,
AMS, PDM, ...)
12.2 Operating keys and DIP switches on the HART electronic insert
Display
onoff
1
2
onoff
3
4
A0046129
 9 Operating keys and DIP switches on the HART electronic insert
1 Operating key for reset password (for Bluetooth login and Maintenance user role)
1+2 Operating keys for device reset (as-delivered state)
2 Operating key II (only for factory reset)
3 DIP switch for alarm current
4 DIP switch for locking and unlocking the device
The setting of the DIP switches on the electronic insert has priority over the settings
made via other operation methods (e.g. FieldCare/DeviceCare).
12.3 Structure and function of the operating menu
The differences between the structure of the operating menus of the local display and the
Endress+Hauser FieldCare or DeviceCare operating tools can be summarized as follows: