Commissioning Micropilot FMR67B HART
34 Endress+Hauser
13.6 Device configuration
13.6.1 Level measurement in bulk solids
100%
0%
R
BD
D
L
F
E
A0016934
 12 Configuration parameters for level measurement in bulk solids
R Reference point of measurement
D Distance
L Level
E "Empty calibration" parameter (= 0%)
F "Full calibration" parameter (= 100%)
13.6.2 Commissioning with the Commissioning wizard
In FieldCare, DeviceCare, SmartBlue and on the display, the Commissioning wizard is
available to guide the user through the initial commissioning steps.
Complete this wizard to commission the device.
For each parameter, enter the appropriate value or select the appropriate option.
NOTE
If you exit the wizard before completing all required parameters, the changes you made will be
saved. For this reason, the device may be in an undefined state!
In this case, a reset to the default settings is recommended.