Micropilot FMR67B HART Commissioning
Endress+Hauser 31
Access is via:
CDI service interface
HART communication
Typical functions:
Parameterization of transmitters
Loading and saving of device data (upload/download)
Documentation of the measuring point
Visualization of the measured value memory (line recorder) and event logbook
For additional information about FieldCare, see Operating Instructions BA00027S and
BA00059S
13 Commissioning
All configuration tools provide a commissioning assistant that supports the user when
setting the most important configuration parameters (Guidance menu Commissioning
wizard).
13.1 Preliminaries
The measuring range and the unit in which the measured value is transmitted correspond to
the data on the nameplate.
L
WARNING
The settings of the current output are relevant for safety!
This can result in product overflow.
The setting for the current output depends on the setting in the Assign PV parameter.
After changing the setting of the current output, check the setting of the span (Lower
range value output and Upper range value output) and change it if necessary!
13.2 Function check
Before commissioning the measuring point, check whether the post-mounting and post-
connection checks (checklist) have been performed:
A
 "Post-mounting check" section
A
 "Post-connection check" section