Commissioning Nivotester FTL325P single-channel
18 Endress+Hauser
7.2.1 Switch position on electronic insert
A
B
A0039743
 13 Switch position on electronic insert (FEL67)
A MAX
B MIN
When using the Liquiphant FTL51B, FTL62, FTL64 sensor with electronic insert FEL67,
sensor (H level) FEL67 must be set to MAX safety and sensor (L level) FEL67 must be set to
MIN safety.
A
B
A0039561
 14 Switch position on electronic insert FEL57
A STD (standard)
B EXT (extended)
This setting is only relevant for the function test.
7.2.2 Switching behaviour and signaling for all functions without fault signaling
See Operating Instructions.