Underspeed Shutdown (Medium Security): a shutdown will occur when the engine speed
reaches this set point. Factory set to 0 RPM
Overspeed Shutdown (Medium Security): a shutdown will occur when the engine speed reaches
this set point. Factory set to 2400 RPM.
High Level Warning (Medium Security): an alarm will occur if the level reaches this set point.
Menu setting shown after analog input is set. Factory set to 0.0 FT
High Level Shutdown (Medium Security): a shutdown will occur if the level reaches this set
point. Menu setting shown after analog input is set. Factory set to 0.0 FT.
Low Level Warning (Medium Security): an alarm will occur if the level reaches this set point.
Menu setting shown after analog input is set. Factory set to 0.0 FT.
Low Level Shutdown (Medium Security): a shutdown will occur if the level reaches this set
point. Menu setting shown after analog input is set. Factory set to 0.0 FT.
High Flow Warning (Medium Security): an alarm will occur if the flow reaches this set point.
Menu setting shown after analog input is set. Factory set to 0 GPM.
High Flow Shutdown (Medium Security): a shutdown will occur if the flow reaches this set
point. Menu setting shown after analog input is set. Factory set to 0 GPM.
Low Flow Warning (Medium Security): an alarm will occur if the flow reaches this set point.
Menu setting shown after analog input is set. Factory set to 0 GPM.
Low Flow Shutdown (Medium Security): a shutdown will occur if the flow reaches this set
point. Menu setting shown after analog input is set. Factory set to 0 GPM.
High Discharge Pressure Warning (Medium Security): an alarm will occur when the pressure
reaches this set point. Factory set to 0 PSI.
High Discharge Pressure Shutdown (Medium Security): a shutdown will occur when the
pressure reaches this set point. Menu setting shown after analog input is set. Factory set to 0
PSI.
Low Discharge Pressure Warning (Medium Security): an alarm will occur when the pressure
reaches this set point. Menu setting shown after analog input is set. Factory set to 0 PSI
Low Discharge Pressure Shutdown (Medium Security): a shutdown will occur when the
pressure reaches this set point. Menu setting shown after analog input is set. Factory set to 0
PSI
High Suction Pressure Warning (Medium Security): an alarm will occur when the pressure
reaches this set point. Menu setting shown after analog input is set. Factory set to 0 PSI.
High Suction Pressure Shutdown (Medium Security): a shutdown will occur when the
pressure reaches this set point. Menu setting shown after analog input is set. Factory set to 0
PSI.
Low Suction Pressure Warning (Medium Security): an alarm will occur when the pressure
reaches this set point. Menu setting shown after analog input is set. Factory set to 0 PSI

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Enovation Controls Murphy PowerCore MPC-10 and is the answer not in the manual?

Enovation Controls Murphy PowerCore MPC-10 Specifications

General IconGeneral
BrandEnovation Controls
ModelMurphy PowerCore MPC-10
CategoryController
LanguageEnglish

Related product manuals