Unit Description, ACCU/DCCU
Terminal block for incoming AC mains cables
Four outgoing cables to the PSUs
Input Data
Table 120
Frequency
45 - 65 Hz
Voltage
90 - 275 V AC
External fuses 4 pcs, max. 16 A
Cable diameter
8.5 - 12.5 mm
Conductor area
1.5 - 2.5 mm
2
Number of conductors 3 (L, N, PE)
Output Data
Four cables with connectors according to IEC 320 and matching the
PSU AC inlet.
Table 121
Conductor area
1.5 mm
2
Number of conductors 3 (L, N, PE)
16.1.3 Dimensions and Weight
Table 122
Height 293.5 mm
Width
141 mm
Depth
60 mm
Weight 5kg
16.2 DCCU
The DCCU consists of a box with:
Terminal block with incoming DC cables
Eight-pole main switch (disconnecting device)
A feed-through capacitor filter
Four cables to the PSUs
16.2.1 Functions
The DCCU has the following functions:
Termination of incoming DC supply cables
Disconnecting incoming DC supply
EMC filtering