General information Safety
3 Safety
3.1 General information
Operation only by trained personnel
The product may be operated by trained adults only.
Training may be provided by the heating technician or
our customer service. Please read the associated doc-
umentation carefully in order to avoid errors during
operation and maintenance.
Persons who lack experience and knowledge as well
as children may not operate, clean, or maintain the
product.
Keep children away from the fuel store and
storeroom
In fuel stores for wood chips, in particular, there is a
danger that a hollow space may form above the
agitator. Children playing on the pile of wood chips, or
careless adults, could fall in and get buried or caught
up in the discharge screw.
Keep fire extinguishers in a clearly visible location
In Austria, the minimum requirement is an
ABC powder extinguisher with 6 kg. An AB foam extin-
guisher with 9 litres, which produces less damage
when used, is preferable. The fire extinguisher should
be kept outside the boiler room, visible and easily
accessible.
Fig. 3-1: Fire extinguisher
In Germany and Switzerland, fire extinguishers are not
required for heating systems in private residences. In
spite of this, we recommend having one in the house.
Storage of ash
The ash must be kept in non-flammable containers
with covers for cooling. Never put hot ash into the
waste bin!
3.2 Safety devices
Pump safety run, automatic heat dissipation at
overtemperature
If the boiler temperature exceeds 90°C (factory setting)
for any reason, the pump safety run will start. All
heating pumps and boiler pumps that are connected to
the boiler control system are switched on to dissipate
heat from the boiler.
This action prevents the boiler temperature from rising
further and triggering further safety devices such as
the safety temperature limiter and the thermal relief
valve.
The heat dissipation is limited by the maximum
flow temperature set in the heating circuits and
the target hot water temperature.
Install thermal emergency cooling valve against
overheating
The safety heat exchanger built into the boiler must be
connected by the heating technician to the house's
cold water supply via a thermal relief valve (opening
temperature 97 °C) to protect the boiler against