Adaptations for
HACK 63-90 kW
Fuel Pellets Wood chips Carpentry material Miscanthus
a
a. Reduced max. output: 65 kW
Water content < 15% < 15% 15 - 25% 25 - 35% < 15% < 20%
Ash/dust content low high low high low high low high low high low high
Software parameters [Fuel] [Pellets] [Woodchips] [Woodchips] [Miscanthus]
Firebed level sensor
Position 2 3 5 3 5
De-ashing interval (boiler with buffer storage tank)
Software parameters
[De-ash after min.] 80 kg 28 kg 35 kg 9 kg 35 kg 9 kg 35 kg 9 kg 17 kg 9 kg 2 kg 2 kg
[De-ash after max.] 120 kg 90 kg 65 kg 33 kg 65 kg 33 kg 65 kg 33 kg 65 kg 33 kg 15 kg 12 kg
De-ashing interval (boiler without buffer storage tank)
Software parameters
[De-ash after min.] 80 kg 57 kg 35 kg 18 kg 35 kg 18 kg 35 kg 28 kg 35 kg 18 kg 5 kg 5 kg
[De-ash after max.] 120 kg 90 kg 65 kg 33 kg 65 kg 33 kg 65 kg 33 kg 65 kg 33 kg 15 kg 12 kg
Boiler with flue gas recirculation installed
Software parameters [Flue gas recirculation] [Yes] [Yes]
[Yes]
(recom-
mended)
[Yes] [No] [Yes] [Yes]
Flue gas recirculation status Open Open
Open
(recom-
mended)
Open Closed Open Open
Boiler without flue gas recirculation
Software parameters [Flue gas recirculation] [No]