ETCR 3000 - V. Measuring Principle

ETCR 3000
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-7-
1. LCD 2. Button area 3. Rotary switch for selecting function
4. RS232 interface 5. Interface of testing wires
6. C(H)interface: Current electrode
7. P(S) interface: Voltage electrode
8. E interface: Earth electrode 9. Testing wires
10. Auxiliary earthing rod 11. Simple earthing wires
12. Testing probe 13. Safety alligator clip
VMeasuring Principle
1. Voltage to ground measurement adopts average value rectification method.
2. Earth resistance measurement with fall-of-potential method. AC constant
current I (3mA Max, 820Hz) is applied between the measurement object E
(earth electrode) and C (current electrode), and finding out the potential
difference V between E and P (potential electrode).
Rx=V/I
3Maximum Operating ErrorOperating error(B) is an error obtained within the
rated operating conditions, and calculated with the intrinsic error(A), which is
an error of the instrument used, and the error(E) due to variations.
A Intrinsic error
E1Variation due to position change
E2Variation due to power supply voltage
E3Variation due to temperature change
E4Variation due to interference voltage change