Information for the Installer (Cont.)
Pipe length and additional refrigerant
Inverter models
capacity (Btu / h)
9K-12K 18K-24K 30-36K
Length of pipe with
standard charge
5m /
16ft
5m /
16ft
5m /
16ft
5m /
16ft
5m /
16ft
5m /
16ft
Length of pipe
with standard
charge (Like: North
American, etc.)
7.5m /
24ft
7.5m /
24ft
7.5m /
24ft
7.5m /
24ft
7.5m /
24ft
7.5m /
24ft
Maximum distance
between indoor and
outdoor unit
15m /
49ft
15m /
49ft
20m /
65ft
20m /
65ft
30m /
98ft
30m /
98ft
Additional refrigerant
charge
20g / m 15g / m 30g / m 25g / m 30g / m 25g / m
Max. diff. in level
between indoor and
outdoor unit
10m /
32ft
10m /
32ft
15m /
48ft
15m /
48ft
20m /
65ft
20m /
65ft
Type of refrigerant
R22/
R410A
R32
R22/
R410A
R32
R22/
R410A
R32
ON/OFF models
capacity
9K-12K 18K-36K
Length of pipe with
standard charge
5m / 16ft 5m / 16ft 5m / 16ft 5m / 16ft
Maximum distance
between indoor and
outdoor unit
15m / 49ft 15m / 49ft 15m / 49ft 15m / 49ft
Additional refrigerant
charge
20g / m 15g / m 30g / m 25g / m
Max. diff. in level
between indoor and
outdoor unit
5m / 16ft 5m / 16ft 5m / 16ft 5m / 16ft
Type of refrigerant R22 / R410A R32 R22 / R410A R32