page 28 of 120
PC46
Pressure set point for high-
temperature pressure-switch control
27.0 0.0 45.0 Bar IS-R
PC47
Pressure differential for high-
temperature pressure-switch control
2.0 0.0 5.0 Bar IS-R
PC48
External high temperature threshold
for pressure-switch control
12.0 -30.0 23.0 °C IS-R
PC49
Min. time for maintaining pressure-
switch partialization
10 0 99 Min. IS-R
PC50
Enabling of low-temperature
pressure-switch control (heat pump)
No (0) No (0) Yes (1) IS-R
PC51
Pressure setpoint for low-temperature
pressure-switch control
3.2 0.0 10.0 Bar IS-R
PC52
Pressure differential for low-
temperature pressure-switch control
2.0 0.0 10.0 Bar IS-R
PC53
External low temperature threshold
for pressure-switch control
-5.0 -10.0 5.0 °C IS-R
PC54
Outlet water high-temperature
threshold for pressure-switch control
48.0 30.0 70.0 °C IS-R
PC55
Delay for partialization from low
pressure alarm
900 0 999 Sec. IS-R
PC61 Summer commutation set point 20.0 PC62 70.0 °C IS-R
PC62 Winter commutation set point 10.0 0.0 PC61 °C IS-R
PC64
Max. dynamic offset compared to
summer set point (chiller)
-10.0 -20.0 20.0 °C IS-R
PC65
Compensation start temperature for
dynamic summer set point
30.0 -15.0 PC66 °C IS-R
PC66
Compensation stop temperature for
dynamic summer set point
60.0 PC65 70.0 °C IS-R
PC67
Max. dynamic offset compared to
winter set point (heat pump)
10.0 -20.0 20.0 °C IS-R
PC68
Compensation start temperature for
dynamic winter set point
0.0 -15.0 PC69 °C IS-R
PC69
Compensation stop temperature for
dynamic winter set point
30.0 PC68 70.0 °C IS-R
PC70
Function limit management:
0 = Heat pump only
1 = Auxiliary output
2 = Auxiliary output and heat pump
0 0 2 IS-R
PC71 Function limit set point -7.0 -30.0 30.0 °C IS-R
PC72 Function limit differential 4.0 0.1 10.0 °C IS-R
PC80 Enabling of control upon request No (0) No (0) Sì (1) IS-R
PC81 Summer setpoint controlupon request 15.0 -15.0 70.0 °C IS-R
PC82 Winter setpoint control upon request 45.0 -15.0 70.0 °C IS-R
PC83
Summer differential control upon
request
4.0 0.1 10.0 °C IS-R
PC84 Winter differential control upon request 4.0 0.1 10.0 °C IS-R
PC85 Delayed control upon request 5 0 999 Sec IS-R
FANS
PF01 Condenser control type 0 0 1 IS-F
0=Modulating
control
1=Single
stage control
PF02 It gives the choice to enable fan Yes (1) No (0) Yes (1) IS-F