control only if at least one compressor
is ON.
PF03
It sets whether or not fans must
switch OFF during defrosting cycles.
No (0) No (0) Yes (1) IS-F
PF07
Min. time which must elapse between
the start-ups of two different fans.
10 0 999 Sec. IS-F
PF08
Min. time which must elapse between
the shutdowns of two different fans.
20 0 999 Sec. IS-F
PF09
Forcing of fans in case of condensing
sensor alarm
No (0) No (0) Yes (1) IS-F
With PF01=0
(Single stage
Control)
PF10
Forcing of fans in case of condensing
sensor alarm
0.0 0.0 100.0 % IS-F
With PF01=1
(Modulating
Control)
PF11
Condensing control set point for
summer operation (chiller)
20.0 5.0 45.0 Bar IS-F
PF12
Linear control band for condensation
in summer operation (chiller)
12.0 0.1 15.0 Bar IS-F
PF13 Enabling of forcing to maximum Yes (1) No (0) Yes (1) IS-F
PF14
Max. forcing enabling set point in
summer operation (chiller)
26.0 15.0 45.0 Bar IS-F
PF15
Disabling differential for max. forcing
in summer operation (chiller)
2.0 0.1 5.0 Bar IS-F
PF16
Integral time for control of valves
(cooling)
0 0 999 Sec IS-F
If PF16=0
Integral action
not present
PF21
Condensing control set point in winter
operation (heat pump)
9.0 0.5 15.0 Bar IS-F
PF22
Linear control band for condensation
in winter operation (heat pump)
2.0 0.1 15.0 Bar IS-F
PF24
Max. forcing activation set point in
winter operation (heat pump,
inverter)
3.2 0.5 20.0 Bar IS-F
PF25
Max. forcing de-activation differential
in winter operation (heat pump,
inverter)
0.5 0.1 5.0 Bar IS-F
PF26
Integral time for control of valves
(heat pump)
0 0 999 Sec IS-F
If PF26=0
Integral action
not present
PF27
Min. value for condenser forcing
(inverter)
0.0 0.0 100.0 % IS-F
PF28
Speed-up time at fan start-up
(inverter)
4 0 999 Sec. IS-F
PF31
Lower limit for condensing linear
control (inverter)
30.0 0 PF32 % IS-F
PF32
Upper limit for condensing linear
control (inverter)
100.0 PF31 100.0 % IS-F
PF33
Enabling of control under the
minimum condensing limit (inverter)
Yes (1) No (0) Yes (1) IS-F
PF34
Switch-off differential under the
minimum condensing limit (inverter)
2.0 0.0 5.0 Bar IS-F
PF36
Enabling of preventilation
0: No
1: Winter only
0 0 2 IS-F