c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 35 of 120
(temperature-pressure conversion).
0: No refrigerant
1: R22
2: R134a
3: R404A
4: R407C
5: R410A
6: R507
R410A
PH32
It sets the temperature measurement
unit:
0: ° Celsius
1: ° Fahrenheit
0 (°C) 0 1 IS-V
PH33
It sets the pressure measurement
unit:
0: Bar
1: psi
0 (Bar) 0 1 IS-V
PH52 It enable the EVCO icon 1 0 1 IS-V
PH53
It sets the meaning of the Summer
and Winter icons.
0: Summer = Cooling (chiller mode)
Winter = Heating (heat pump
mode)
1: Summer = Heating (heat pump
mode)
Winter = Cooling (chiller mode)
0 0 1 IS-V
PH90 Language Eng Eng Ita IS-V
PH99
CANbus BaudRate:
(1=20K; 2=50K; 3=125K; 4=500K)
2 (50K) 1 4 IS-V
PSd3
It sets the Installation Operator level
password.
0 -999 9999 IS-V
Level
4
CONFIGURATION MENU
CONFIGURATION
PGUT Unit type setting 10 1 16 CO-W
PG00
It sets the unit type:
1: Air-to-water chiller
2: Air-to-water chiller + heat pump
3: Water-to-water chiller
4: Water-to-water chiller + heat
pump
1 1 4 CO-W
PG01 Number of circuits 2 1 2 CO-W
PG02
It enables the presence of the IO
expansion.
Yes (1) No (0) Yes (1) CO-W
PG03
It sets the number of compressors
per circuit.
3 1 3 CO-W
PG04 Enable Real Time Clock-RTC 1 0 1 CO-W
PG05
Enable the presence of the EVCM
Modules (1 per circuit)
Yes (1) No (0) Yes (1) CO-W
PG09 It sets the number of pumps. 1 1 2 CO-W
PG10
Sets the number of source pumps (for
water-water unit)
1 1 2 CO-W
Only for
Water-Water
unit
PG11
It enables unique condensing:
0: No (2 fans)
No (0) No (0) Yes (1) CO-W
For Water-
Water