EVCO S.p.A.
c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104
page 36 of 120
1: Yes (1 fan) unitdetermine
s whether
there are1/2
heat source
exchangers
PG12
It enables single/twin
exchangerusers:
0: No (2)
1: Yes (1)
Yes (1) No (0) Yes (1) CO-W
Determines
whether there
are1/2heat
sink
exchangers
PG13
Set the type of free-cooling air circuit
0: Only with condensation
1: Separate with AO fan
2: Separate with DO fan
1 0 2 CO-W
Only for
Chillers Air-
Water unit
PG14
It enables
single/twinexchangersource:
0: No (2)
1: Yes (1)
Yes (1) No (0) Yes (1) CO-W
Determines
whether there
are 1/2heat
source
exchangers
PSd4 Constructor level password 0 -999 9999 CO
HARDWARE CONFIGURATION
HA01
HA02
HA03
HA07
HA08
HA09
They set the probes connected to
analog inputs 1, 2, 3, 7, 8, 9 of the
controller
3
4
13
0
0
0
0 68 CO-HW
See Table
Config. AI
HA04
HA05
HA06
They set the probes connected to
analog inputs 4,5,6 of the controller
10
0
0
0 56 CO-HW
HA11
HA12
HA16
HA17
HA18
HA19
They set the probes connected to
analog inputs 1, 2, 3, 7, 8, 9 of the
expansion
15
11
0
0
0
0
0 68 CO-HW
HA13
HA14
HA15
They set the probes connected to
analog inputs4,5,6 of the expansion
0
0
0
0 56 CO-HW
HB01
HB09
They set which digital resources to
connect to the digital inputs of the
controller
3
7
11
27
21
23
25
15
9
0 44 CO-HW
See Table
Config. DI
HB10
HB18
They set which digital resources to
connect to the digital inputs of the
expansion
39
33
35
37
0
0
0
0 44 CO-HW