0
0
HC01
HC02
HC03
HC04
They set which analog resources to
connect to analog outputs
1, 2, 3, 4 of the controller
4
6
0
0
0 9 CO-HW
See Table
Config. AO
HC07
HC08
HC09
HC10
They set which analog resources to
connect to analog outputs
1, 2, 3, 4 of the expansion
0
0
0
0
0 9 CO-HW
HC05
HC06
They set which analog resources to
connect to analog outputs
5, 6 of the controller
0
0
0 6 CO-HW
HC11
HC12
They set which analog resources to
connect to analog outputs
5, 6 of the expansion
0
0
0 6 CO-HW
HCF1
It sets the frequency of the PWM
function of theFree Cooling fan
1000 10 2000 Hz CO-HW
HCF2
It sets the frequency of the PWM
function of the circuit 1 fan
1000 10 2000 Hz CO-HW
HCF3
It sets the frequency of the PWM
function of the circuit 2 fan
1000 10 2000 Hz CO-HW
HD01
…
HD09
They set which digital resources to
connect to the digital outputs of the
controller
2
12
14
26
6
22
0
0
0
0 48 CO-HW
See Table
Config. DO
HD10
…
HD18
They set which digital resources to
connect to the digital outputs of the
expansion
30
32
40
0
0
0
0
0
0
0 48 CO-HW
ELECTRONIC VALVE MODULES
EVDRIVE03 circuit 1
PV01 Setpoint SH (1) 6.0 3.0 25.0 K CO-V
PV02 Setpoint LoSH (1) 2.0 1.0 3.0 K CO-V
PV03 Setpoint HiSH (1) 15.0 10.0 40.0 K CO-V
PV04 Setpoint LOP (1) -40.0 -40.0 40.0 K CO-V
PV05 Setpoint MOP (1) 40.0 -40.0 40.0 K CO-V
PV06 PID – proportional band (1) 7.0 1.0 100.0 K CO-V
PV07 PID – integraltime (1) 120 0 999 sec CO-V
PV08 PID – derivative time(1) 120 0 999 sec CO-V
PV09 Start-up delay (1) 5 1 255 sec CO-V
PV10 Start-up position (1) 50.00 0.00 100.00 % CO-V
PV11 Setpoint SH (2) 6.0 3.0 25.0 K CO-V
PV12 Setpoint LoSH (2) 2.0 1.0 3.0 K CO-V