EV3 MVC & EVD MVC | Application manual ver. 2.2c | Code 1443DMVCI224
page 57 of 74
Label Visibility default min max UM description
S03 U
Alarm in progress
0: OFF
1: ON
S04 U
Operating mode
0: Disabled
1: OFF
2: Comfort
3: Economy
4: Night
5: Holiday:
6: Manual
7: Holiday with machine off
255: None
S05 S 0 100 % Fan Regulation Setpoint
S06 S
Fan operating mode
0: Normal
1: Remote
2: CO2
3: Humidity
4: Forced by DI
5: OFF - External air damper awaited
6: Alarm
7: OFF
8: OFF from digital input (DI)
9: OFF from time band (TB)
10: External air limitation
11: Constant pressure
12: Constant capacity
13: OFF - Defrosting
14: ON - Defrosting
15: 15 = Post-ventilation
S07 U % Supply Fan Speed
S08 U % Return Fan Speed
S09 S 0 100 % Mixing chamber damper regulation setpoint
S10 S
Mixing chamber damper operating mode
0: Disabled
1: Normal
2: CO2
3: Humidity
4: Free cooling/heating
5: OFF
6: External air limitation
S11 S % Mixing chamber damper aperture
S12 S
Recovery heat exchanger operating mode
0: Disabled
1: OFF
2: ON
S13 S % Recovery heat exchanger percentage
S14 S
Recovery heat exchanger defrost phase
0: Not in defrost
3: Defrosting
5: Dripping
S15 U 0 100 80 %rH Humidity setpoint