8.2 Thawing
Pressing this area enables selection of a thawing cycle, managed according to the load of product to be thawed, in
compliance with the maximum quantity stated by the manufacturer.
Where possible, a slow-cooking phase or a slow cooking + holding phase can be combined with thawing.
To make it easy, the quantity of product to be selected is divided into three load bands for each of which the controller
will load three different sets of parameters, according to the following framework.
Load band Initial cabinet set point Final cabinet set point Cycle duration
Lightly loaded r25 r28 r32
Partly loaded r26 r29 r33
Full loaded r27 r30 r34
These three parameters will be used to control the working cabinet set points and the duration of the thawing cycle,
equally divided into five phases following on from each other as shown.
- Phase 1 working set point = initial set point
- Phase 2 working set point = phase 1 set point - [(initial set point – final set point) / 4]
- Phase 3 working set point = phase 2 set point - [(initial set point – final set point) / 4]
- Phase 4 working set point = phase 3 set point - [(initial set point – final set point) / 4]
- Phase 5 working set point = final set point