EasyManua.ls Logo

Evinox ModuSat XR - Pressure Independent Control Valve

Evinox ModuSat XR
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29 2551868AB
Pressure independent control valve
Heating PICV set points (if required)
Pre-set
Flow l/h
Pre-set
Flow l/h
0.5
2.2
324
0.6
100
2.4
351
0.8
128
2.6
379
1.0
156
2.8
407
1.2
184
3.0
445
1.4
212
3.2
463
1.6
240
3.4
491
1.8
268
3.6
519
2.0
296
3.8
547
2.2
324
4.0
575
Valve Tolerances
The maximum flow rate will vary depending on the varying differential pressure
across the units and the resulting flow rate may differ from the value shown
above. The valve should be set to 125% above the design flow rate. The project
specific set-point (if required) can be confirmed by Evinox Energy.
Tighten Actuator Connections
Ensure that the actuators are tightened to ensure the operation of the unit.
DHW PICV (TP-30/55/70)
DHW PICV (TP-100)
HTG PICV
Maximum flow rate
1600 l/h +/- 10%
3609 l/h +/- 10%
575 l/h +/- 10%
Start up ∆P
25 kPa
25 kPa
25 kPa
Max differential ∆P
400 kPa
400 kPa
400 kPa
Valve size
DN20
DN25
DN15
Thread
G 1
G 1 1/4”
G 3/4’
Actuator Stroke
2.5 mm
5.5 mm
2.5 mm
Actuator control signal
0-10V
0-10V
0-10V
Mechanical pre-setting
Not available
Available
Available