FSW
STP CL OP
How to connect Normally Open contacts.
(Connect them in parallel)
How to connect Normally Close contacts.
(Connect them in series)
The photocells must be connected depending on which area
they must protect. (See Fig. A5)
Closing Safety D : These photocells protect the area covered
by the gate during the closing movement. They have no effect
during the opening movement.
Opening Safety B-C : These photocells protect the area covered
by the gate during the opening movement. They have no effect
during the closing movement.
Opening/Closing Safety A : These photocells protect the area
covered by the gate both during the opening and the closing
movements.
The E024U board allows the connection of several safety devices
(for example photocells). With photocells you can activate the
FAILSAFE function, which, before each movement of the ope-
rator, tests each fotocells. In case the test fails the movement
is inhibited. To activate this function set to ON the dip-switch N.
11 and 12 of DS1, and connect the negative of the transmitter
to the OUT pin (No.9)
.
Fig. A3
Fig. A5
Fig. A4
Connection of a pair of closing photocells and a pair of opening/closing photocells
To use the FAIL-
SAFE mode con-
nect the negative
power supply of the
transmitters to OUT
(pin 9), and set dip-
switch 11 and 12 to
ON on DS1
Fig. A6
RX= Photocell Receiver
TX= Ptotocell Transmitter
CL= Closing
OP= Opening
3. PHOTOCELLS CONNECTIONS
3.1 CONNECTIONS TO NORMALLY CLOSE (N.C.) PHOTOCELLS
A4
E024U CONTROL BOARD