EasyManua.ls Logo

FCI FLT93S - Flow Element Diagnostics

Default Icon
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATION FLT
®
Series FlexSwitch
TM
34 Fluid Components International LLC
Fail-Safe Alarm Setting
These procedures set the second relay to detect component failure (fail-safe).
Low Flow Alarm Settings
Install the following jumpers for the low flow fail-safe setup: J18, J20, J23, J24, J27.
The following information is assumed:
Relay is de-energized in the ALARM condition.
Alarm 1 setpoint is adjusted for desired low flow alarm velocity or signal.
Alarm 2 setpoint is adjusted slightly below minimum signal output (over range flow).
High Flow Alarm Settings
Install the following jumpers for the high flow fail-safe setup: J18, J20, J23, J25, J26.
The following information is assumed:
Relay is de-energized in the ALARM condition.
Alarm 1 setpoint is adjusted for desired high flow alarm velocity or signal.
Alarm 2 setpoint is adjusted above maximum signal output (under range flow not to exceed 7.0 volts).
Figure 3-5. Low Flow Fail-Safe Alarm
Figure 3-6. High Flow Fail-Safe Alarm

Related product manuals