2-3 Parameter functions and method of settings
Method of setting the SV (Setting value)
[Description]
•The SV is a target value for control.
•Any SV that is outside of the range set in the parameters
of (lower limit) and (upper limit) of the
third block cannot be set. (See page 54.)
[Setting example] Changing the SV from 250°C to 1195°C
Press the or keys to display .
will be registered in the SV (SV0) in three seconds. After that, the controller will operate
with the SV being 1195.
Operating procedureDisplay
1.
2.
SV
SV
Related parameters: (page 54)
(page 54)