17
ADVANCED PARAMETERS
26. THRESHOLD UP value - „On/O (Power)” association group (3)
The value of BASIC SET command frame sent to the devices associat-
ed in 3rd group „On/O (Power)”
if power exceeded value of param-
eter 21
.
Available settings: 0-99 or 255
Default setting: 255 Parameter size: 2 [bytes]
27. THRESHOLD DOWN value - „On/O (Power)” association
group (3)
The value of BASIC SET command frame sent to the devices associ-
ated in 3rd group „On/O (Power)” i
f power dropped below value of
parameter 22
.
Available settings: 0-99 or 255
Default setting: 0 Parameter size: 2 [bytes]
ALARMS
30. Active alarms
Dene Z-Wave network alarms to which the Wall Plug will respond.
Available settings: 1 - general alarm
2 - smoke alarm
4 - CO alarm
8 - CO2 alarm
16 - high temperature alarm
32 - ood alarm
Default setting: 63 (all) Parameter size: 1 [byte]
31. Response to alarm frames
This parameter denes how the Wall Plug will respond to alarms (de-
vice’s status change).
In case of values 1 or 2 the Wall Plug is operating normally and LED
frame signals an alarm through time dened in parameter 32 or until
the alarm is canceled.
In case of values 5 to 50 the Wall Plug does not report status change,
power changes, ignores BASIC SET command frames. After time de-
ned in parameter 32 or after the alarm cancellation, connected de-
vice is set to the previous state.
Available settings: 0 - no reaction,
1 - turn connected device on
2 - turn connected device o
5-50 (0.5-5.0s, step 0.1s) - cyclically change de-
vice state with set period
Default setting: 0 Parameter size: 1 [byte]