Application Guide
Form No. 06-795, Rev. 0 (02/16)
Page 1 of 8
Figure 1 - Model TA-123PP
Cheetah
®
Xi and SHP-Pro
®
Purge Operation
The National Fire Protection Association (NFPA) standards associated with gaseous fire suppression systems (e.g.,
carbon dioxide and clean agent) stipulate that suitable steps and safeguards shall be taken to prevent injury or death
to personnel in areas whose atmospheres will be made hazardous by the discharge or thermal decomposition of the
agent. One of the recommended safeguards includes providing a means for prompt ventilation (purge) of the fire zone
after an event has occurred.
In the past, Fike offered a self-contained purge panel (P/N 10-045) that could be installed to meet this requirement;
however, the purge panel has been discontinued and is no longer available from Fike. This does not mean that Fike’s
releasing systems are no longer able to comply with the purge requirement. It simply means that an alternate method
must be used, as described in this application guide, to accomplish the purge requirement. There are two options that
can be used to perform the purge function with Fike’s suppression panels.
Option 1
The first option is to purchase and install the Purge Panel Controller, model TA-
123PP, manufactured by Light Engineered Displays, Inc. (See Figure 1). One
controller must be purchased for each suppression zone and external field
relays must be installed to control the purge components. The L.E.D. purge
controller has been tested by Fike for compatibility and correct operation with
both the Cheetah Xi (including 50 point) and SHP-Pro panels. The purge
controller must be purchased directly from L.E.D. and not from Fike.
Note: This is the only option for performing purge with the SHP-Pro panel.
Option 2
The second option is to utilize the following Cheetah Xi components to accomplish the purge functionality.
2 ea. 55-043 relay module,
1 ea. 55-045 mini-monitor module,
1 ea. 20 Zone annunciator 10-2667,
1 ea. Key-Switch (non-latching capable)*
*The 10-1642 Keyed Abort or 10-2705 Solenoid Disconnect switches can be used for this purpose but would need to
re-label for purge functionality.
General Purge Sequence of Operation
Upon the suppression zone entering into the “Release State”, the following shall occur:
1. A relay module configured for “Release” for the active suppression zone will activate. The relay shall be
configured with a time delay (0 to 80 minutes) for “Purge Soak”.
2. An LED on a twenty-zone annunciator will illuminate to indicate the start of the “Purge Soak” period for the
suppression zone.
3. Upon completion of the “Purge Soak” timer, the relay module’s contacts (item 1) will transfer sending a
“Process” input to the panel via the modules feedback input. This input will be the first interlock required to
initiate purge operation.
4. An LED on a twenty-zone annunciator will illuminate to indicate the completion of the “Purge Soak” period and
the ready state of the purge system.
5. Upon activation of a purge key-switch (non-latching) configured for the suppression zone, a “Process” input
will be sent to the panel. This input will be the second interlock required to initiate purge operation.

Other manuals for Fike Cheetah Xi

Question and Answer IconNeed help?

Do you have a question about the Fike Cheetah Xi and is the answer not in the manual?

Fike Cheetah Xi Specifications

General IconGeneral
TypeFire Alarm Control Panel
Power Supply24 VDC
AnnunciatorsUp to 32 remote annunciators
Operating Voltage120/240 VAC, 50/60 Hz
Operating Temperature0°C to 49°C (32°F to 120°F)
Enclosure RatingNEMA 1
Humidity Range0 to 93% RH, Non-condensing
Input ChannelsConfigurable
Output ChannelsConfigurable per SLC loop
WeightApproximately 15 lbs
SLC Loops2
Dimensions14.5" H x 12.5" W x 3.5" D (36.8 cm x 31.8 cm x 8.9 cm)

Summary

Fike Purge Operation: Cheetah Xi & SHP-Pro

Option 1: External Purge Panel Controller

Details the use of the TA-123PP Purge Panel Controller from Light Engineered Displays, Inc.

Option 2: Internal Cheetah Xi Components

Outlines using Cheetah Xi components for purge functionality.

General Purge Sequence of Operation

Explains the step-by-step sequence for purge operation activation.

Panel Programming for Purge Functionality

Configuring Relay Module for Purge Soak

Configures a relay module for the 'Purge Soak' period, detailing common and miscellaneous options.

Wiring Relay Module for Purge Soak

Details the wiring configuration for the 'Purge Soak' relay module.

Configuring Monitor Module for Purge Activation

Configures a monitor module for purge activation, including input and relay settings.

Configuring Second Relay Module for Purge Operation

Configures a second relay module for activating purge system components.

Purge System Status Indication

20-Zone LED Annunciator Programming

Programming the 20-Zone remote LED annunciator for purge system status.

LED Annunciator Labeling

Labeling for the 20-Zone remote LED annunciator to indicate LED meanings.

Related product manuals