EasyManua.ls Logo

Fire-Lite MS-9050UDC - Page 49

Fire-Lite MS-9050UDC
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
MS-9050UD Series PN 52413:D 12/15/08 49
Before installing the module, place the disconnect switch to the right (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the MS-9050UD. In addition, the System Trouble LED will turn on
to indicate the Disconnect condition.
Figure 2.10 4XTMF Transmitter Module
Connect to FACP J8 & J9
Disconnect Switch
shown in disconnect
position
TBL Jumper
}Remote Alarm (power-limited)*
}Remote Trouble (power-limited)*
No connection
}Municipal Box (nonpower-limited)*
1 2 3 4 5 6 7
+ - + - + -
Polarities are shown for module activation
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application using reverse polarity of a supervisory
signal, refer to "FACP with Keltron" on page 195.
* Wiring from these
terminals can exit the
protected premises.
Dummy load terminals
6 and 7 (4.7kΩ, ¼ watt
resistor) if Municipal
Box is not connected.
Disconnect LED
4xtmfl.cdr

Table of Contents

Related product manuals