MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 13
Features and Options Product Description
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire or
3,000 ft (900 m) with untwisted, unshielded wire
Single standard addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
Optional module for adding a second SLC loop which meets NFPA Style 4, 6 and 7
requirements
318 addressable device capacity for each SLC loop (159 detectors and 159 control/monitor
modules)
99 software zones
Up to four onboard NACs (Notification Appliance Circuits):
four Style Y (Class B) or two Style Z (Class A)
Additional NAC capability using control modules
7.0 amps total power for NACs and 24 VDC auxiliary power outputs in alarm
Two programmable relay outputs and one fixed trouble relay
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
New ANN-BUS Annunciators/Modules (ACS annunciators cannot be used when ANN-BUS
annunciators/modules are connected)
ANN-80 Remote Liquid Crystal Display point annunciator
ANN-I/O LED Driver Module
ANN-LED Alarm, Trouble, Supervisory Annunciator (minimum of one required for
Canadian applications)
ANN-RLED Alarm Annunciator
ANN-S/PG Serial/Parallel Printer Module
ANN-RLY Form-C Relay Module
Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
Legacy ACS/Term Annunciators: (ANN-BUS annunciator/modules cannot be used when
ACS/Term annunciators are connected)
ACM Series-LED Zone Annunciators
LDM Graphic Annunciator Series
LCD-80F Liquid Crystal Display point annunciator (LCD-80FC for Canadian applications)
ACM-8RF Relay Module
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-
stage capability

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite MS-9600UDLS and is the answer not in the manual?

Fire-Lite MS-9600UDLS Specifications

General IconGeneral
BrandFire-Lite
ModelMS-9600UDLS
CategoryControl Panel
LanguageEnglish

Related product manuals