MS-9600LS Series Manual — P/N 52646:B8 11/20/2015 135
Coded Operation Operating Instructions
4.18 Coded Operation
The NAC circuits resident on the control panel main circuit board can be programmed for coded
operation. The available pulse rates which can be programmed for coded operation are as follows:
Continuous: Steady output with no pulsing
March Time: Pulses at 120 ppm (pulses per minute)
Temporal Code: Pulses at ½ second On, ½ second Off, ½ second On, ½ second Off,
½ second On, 1½ second Off
California Code: 10 seconds On, 5 seconds Off
Two-Stage Pulses at 20 ppm (pulses per minute) for 5 minutes and
then changes to Temporal
4.19 Presignal
Presignal option programs an initiating device to delay the activation of NACs and/or control mod-
ules while allowing visual verification by a person. Once a detector or monitor module triggers an
alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user pro-
grammed time duration of up to three minutes. Note that the alarm relay and communicator will
respond to the initial alarm immediately. In addition, Zone 98 will activate. This zone can be pro-
grammed to a control module which may be used to activate a sounder or indicator which the
installer designates as a Presignal indication. Do not assign Zone 98 to a Notification Appliance
Circuit when using this zone to indicate a Pre-signal condition.
After the programmed delay, the NACs will activate if the source of the alarm is not cleared. Note
that if a second alarm occurs during the programmed time delay, the alarm will be processed imme-
diately, causing activation of the appropriate output zones. The events which occur upon Presignal
activation are as follows:
onboard piezo sounds immediately
control panel LCD display will indicate a presignal event and the active point
control points programmed to Zone 98 will activate
annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED
outputs (NACs and control modules) of associated zones will be inhibited from activating
for a user programmed time delay of up to three minutes
second alarm occurring anytime during the time delay will cause immediate activation of all
associated outputs
Presignal does not affect monitor modules programmed as waterflow, supervisory, process moni-
toring or remote switches. Presignal operation requires the approval of the local Authority Having
Jurisdiction.
4.20 Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds. Zone 97, however, will acti-
vate immediately and may be used to connect a signaling device to indicate PAS activation. Do not
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion.
When a detector triggers an alarm, the onboard piezo sounds immediately, but the NACs are pre-
vented from activating for 15 seconds. This inhibit time is factory set and cannot be changed. Press-
ing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence the
piezo sounder and start a timer which prevents activation of NACs for an additional time duration
which can be user programmed for up to three minutes. After the programmed delay, the NACs will

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite MS-9600UDLS and is the answer not in the manual?

Fire-Lite MS-9600UDLS Specifications

General IconGeneral
BrandFire-Lite
ModelMS-9600UDLS
CategoryControl Panel
LanguageEnglish

Related product manuals