67C Series
4















Before installing a Type 67C, 67CR, 67CS, 67CSR, 
67CF, 67CFR, 67CFS, or 67CFSR regulator, be 
sure the installation complies with the following
installation guidelines:
1.  Regulator operation within ratings does not           
preclude the possibility of damage from debris in
       the lines or from external sources.  Regulators  
should be inspected for damage periodically and
after any overpressure condition.
2.  Only personnel qualied through training and  
experience should install, operate, and maintain
a regulator. Make sure that there is no damage to
       or foreign material in the regulator.  Also ensure  
that all tubing and piping is free of debris.
3.  Install the regulator so that ow is from the IN to
the OUT connection as marked on the regulator body.
4. For best drainage, orient the drain valve (key 2) to
the lowest possible point on the dripwell (key 5). This
orientation may be improved by rotating the dripwell
with respect to the body (key 1).
!

Types 67CR, 67CSR, 67CFR, and 67CFSR have 
a low capacity internal relief valve for minor seat
leakage only. Other overpressure protection must be
provided if the maximum inlet pressure can exceed
the maximum pressure rating of the downstream
equipment or exceeds the maximum outlet pressure
rating of the regulator.


























Table 1. Outlet Pressure Ranges and Control Spring Data
Types



    
67C, 67CR, 
67CF, 67CFR
0 to 20
0 to 35
0 to 60
0 to 125
(0 to 1,4)
(0 to 2,4)
(0 to 4,1)
(0 to 8,6)
Green stripe
Silver
Blue stripe
Red stripe
Music
Wire
GE07809T012
T14059T0012
T14058T0012
T14060T0012
0.135
0.156
0.170
0.207
(3,43)
(3,96)
(4,32)
(5,26)
1.43
1.43
1.43
1.43
(36,2)
(36,2)
(36,2)
(36,2)
0 to 35
0 to 60
0 to 125
(0 to 2,4)
(0 to 4,1)
(0 to 8,6)
Silver stripe
Blue
Red
Inconel
®
T14113T0012
T14114T0012
T14115T0012
0.156
0.172
0.207
(3,96)
(4,37)
(5,26)
1.43
1.43
1.43
(36,2)
(36,2)
(36,2)
67CS, 67CSR, 
67CFS, 67CFSR
0 to 20
0 to 35
0 to 60
0 to 125
0 to 150
(0 to 1,3)
(0 to 2,4)
(0 to 4,1)
(0 to 8,6)
(0 to 10,3)
Green
Silver stripe
Blue
Red
Black
Inconel
®
10C1729X012
T14113T0012
T14114T0012
T14115T0012
10C1730X012
0.135
0.156
0.172
0.207
0.250
(3,43)
(3,96)
(4,37)
(5,26)
(6,35)
1.50
1.43
1.43
1.43
1.77
(38,1)
(36,2)
(36,2)
(36,2)
(44,9)
Inconel
®
is a marked own by Special Metals Corporation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher 67CFR and is the answer not in the manual?

Fisher 67CFR Specifications

General IconGeneral
Model67CFR
ManufacturerFisher
Temperature Rating-20 to 180°F
Temperature Capabilities-20° to 180°F
Body MaterialAluminum
MaterialAluminum
Connection Type1/4" NPT

Related product manuals