EasyManua.ls Logo

FLIR ThermaCAM EX300

FLIR ThermaCAM EX300
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The start of the overheat condi-
tion. This must be carefully
monitored.
< 5°C (9°F)I
Developed overheating. It must
be repaired as soon as possible
(but think about the load situa-
tion before a decision is made).
5–30°C (9–54°F)II
Acute overheating. Must be re-
paired immediately (but think
about the load situation before
a decision is made).
>30°C (54°F)III
7
Publ. No. 1558439 Rev. a156 ENGLISH (EN) February 28, 2006 27
7 Introduction to thermographic inspections of electrical installations

Table of Contents

Related product manuals